Przeglądanie stron 0
Motogard
Series 150
CONNECTIONS
Power Connections:
Connect 120/240 VAC to input terminals 1 and 2.
Sensor Connections:
1. Connect one lead of each thermistor to Terminal 3.
2. Connect other lead of each Thermistors in series through to Terminal 4.
3. Maximum number of Thermistors in series: Three (3)
Output Load Connections:
1. Terminals 5, 6 and 7 comprise a set of “form C” contacts with terminal 6 common.
Terminal 5 is the open side. Terminal 7 is the closed side.
2. Be sure power is never applied directly across contacts but always in series with a load.
3. Maximum allowable load - 5 amps at 115 VAC
4. The closed output of the Motogard Over Temperature Protection System has been
specifically designed to operate directly in series with most main line contactors. If a small
interposing relay must be used, the sealed burden should be greater than 10VA.
5. The open output of the Series “150” controller can be used for trip indication.
See opposite side for possible wiring option.