Installation and Maintenance Manual
Chapter 3: Programming
3.15: Power-Up in a Position or RPM
The 1995A can power up displaying either Position or RPM data.
The power-up mode is programmed by entering the following:
A) Unit must be in the Program mode.
B) Depress . If a zero (0) is entered,
ENT
CIR#
-
1
-
6 3
--
(0 or 1)
-
ENT
-
positional data will be displayed upon power-up; if a one (1) is entered, the unit will power up
displaying RPM.
3.16: Decimal Point Programming
A continuous, nonfloating decimal point may be programmed on the display. If a scale factor is selected
that needs a decimal point in order to properly display its resolution in engineering units, the following 50
series codes are used:
50 - No decimal point;
clears existing decimal point 123
51 - Tenths 12.3
52 - Hundreths 1.23
To program a decimal point, enter the following:
A) Unit must be in the Program mode.
B) Depress .
Example: CIR# 50 = 123
CIR# 51 = 12.3
CIR# 52 = 1.23
ENT
CIR#
-
50
or
51 52
or -