ReFlex Power™ Programming Manual Fixed Power DC Remote Programming
128 M380056-03 Rev L
6.6
OUTPUT SCPI COMMANDS
6.6.1 OUTPUT
SCPI
C
OMMAND
S
UMMARY
OUTPut<n>
:STATe <bool>
:STATe?
:ISOLation?
:SENSe <bool>
:SENSe?
6.6.2 OUTPUT
SCPI
C
OMMAND
R
EFERENCE
OUTPut<n>
OUTPUT subsystem of commands
:STATe <bool>
Turns the output On or Off. Valid arguments are 1/On (Output On)
or 0/Off (Output Off).
:STATe?
Returns the state of the Output, 1 = On, or 0 = Off.
:ISOLation?
Returns the state of the ISOL relay, Open if Output is off.
:SENSe <bool>
Opens/Closes the SENSe relay.
:SENSe?
Returns the state of the SENSe relay
Note: The Fixed Power module powers up with sense relays closed. If the external
sense lines are not connected, the module may fault off. If you do not want to run
sense lines to the load then connect them locally. The relay states are saved then
restored across module disable/enable transitions.