ReFlex Power™ Programming Manual Controller Module Remote Programming
26 M380056-03 Rev M
With authorized log-in (default parameters: User ID = admin; Password =
password), click the IP CONFIGURATION tab (Figure 2-6) where you can
customize the Host Name and Description, and/or select Use a Static IP
Address (Figure 2-7) to change IP Address, Subnet Mask, Gateway, DNS
Server and Listening Port. Please ask your IT Administrator for support.
2.5.3 IP
C
ONFIGURATION
The default IP Address configuration is DHCP-enabled and Auto IP-enabled. If
a DHCP server is not found, an address in the range of 169.254.[1 thru 254].[0
thru 255] will be selected. If there is no DHCP server on your local network,
your PC must also be configured for Auto-IP for the RFP system to be
discovered. For only DHCP, select “Obtain an IP Address Automatically” and
deselect “Auto IP Enabled”). Click the APPLY button to set your inputs.
Figure 2-6. IP CONFIGURATION Page, Default