AMETEK Programmable Power BPS / MX / RS Series SCPI Programming Manual
204 Manual P/N 7003-961 Rev AA
REGenerate:OUTPut[:STATe]
This command enables or disables the source regenerate mode. When the regenerate
mode is OFF (disabled), the MX/RS behaves like a standard MX/RS without the SNK option.
In order to turn on the REGENERATE mode of operation (enable), the output relay has to be
open and the programmed frequency has to be within a 40 – 80Hz range. The query form
returns the regenerate state.
Command Syntax REGenerate:OUTPut[:STATe]<bool>
Parameters 0 | OFF | 1 | ON
Examples REG:OUTP 1 REG:OUTP:STAT ON
Query Syntax REG:OUTPut[:STATe]?
Returned Parameters 0 | 1
REGenerate:OVER[:VOLTage]
This command will set or query the upper voltage limit over which the EUT is allowed to
operate.
Command Syntax REGenerate:OVER[:VOLTage] <Nrf+>
Parameters 0 to max. value for selected voltage range.
Examples REG:OVER:VOLT 120
Query Syntax REGenerate:OVER[:VOLTage]?
Returned Parameters <NR2>
REGenerate:UNDer[:VOLTage]
This command will set or query the lower voltage limit over which the EUT is allowed to
operate.
Command Syntax REGenerate:UNDer[:VOLTage] <Nrf+>
Parameters 0 to max. value for selected voltage range.
Examples REG:UND:VOLT 120
Query Syntax REGenerate:UNDer[:VOLTage]?
Returned Parameters <NR2>